DC current transducer
CHZ-2000AY1, 3000AY1, 5000AY1
Sensor Module |
CHZ-2000AY1、3000AY1、5000AY1 |
||||
Description |
The SENSOR Module CHZ-AY1 is a DC current transducer to measure 2000A…5000A DC currents with a galvanic isolation between the primary and secondary circuits. The output of thetransducer is a standard DC signal. The aperture can be opened by a structure of a split core for easy installation. |
||||
|
|||||
DC Current Transducer(Output 0…20mA): |
|||||
Type |
Nominal current |
Output current |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
IM(mA) |
X(%) |
Vc(V) |
mm/split core |
|
CHZ-2000AY1/A0 |
2000 |
0…20 |
±1.0% |
±12~15 |
50X165 |
CHZ-3000AY1/A0 |
3000 |
|
|
|
|
CHZ-5000AY1/A0 |
5000 |
|
|
|
|
|
|||||
DC Current Transducer(Output 4…20mA): |
|||||
Type |
Nominal current |
Output current |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
IM(mA) |
X(%) |
Vc(V) |
mm/split core |
|
CHZ-2000AY1/A1 |
2000 |
4…20 |
±1.0% |
±12~15 |
50X165 |
CHZ-3000AY1/A1 |
3000 |
|
|
|
|
CHZ-5000AY1/A1 |
5000 |
|
|
|
|
|
|||||
DC Current Transducer(Output 0…5V): |
|||||
Type |
Nominal current |
Output voltage |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
VM(V) |
X(%) |
Vc(V) |
mm/split core |
|
CHZ-2000AY1/V0 |
2000 |
0…5 |
±1.0% |
±12~15 |
50X165 |
CHZ-3000AY1/V0 |
3000 |
|
|
|
|
CHZ-5000AY1/V0 |
5000 |
|
|
|
|
|
|||||
DC Current Transducer(Output 1…5V): |
|||||
Type |
Nominal current |
Output voltage |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
VM(V) |
X(%) |
Vc(V) |
mm/split core |
|
CHZ-2000AY1/V1 |
2000 |
1…5 |
±1.0% |
±12~15 |
50X165 |
CHZ-3000AY1/V1 |
3000 |
|
|
|
|
CHZ-5000AY1/V1 |
5000 |
|
|
|
|
|
|||||
Specifications: |
|||||
Principle |
Hall effect sensor + Transducer |
||||
Input current |
2000A…5000A(DC) |
||||
Output |
One of A0=0~20mA、A1=4~20mA、V0=0~5V、V1=1~5V(DC) |
||||
Frequency |
DC |
||||
Accuracy |
±1.0% |
||||
Response time |
<350mS |
||||
Linearity |
<0.5% |
||||
Supply voltage |
±12V…15V(±5%) |
||||
Consumption |
30mA+IM(Output current) |
||||
Isolation voltage |
Between primary and secondary circuit: 5KV RMS/50Hz/1min. |
||||
Operating temp. |
-25℃ …+85℃ |
||||
Applications |
The sensors are used in the industry field of power supplies, welding machines, converters, |
||||
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc. |
||||
|
|||||
Dimensions(mm) & Connection: |
|||||
|
Contact: Mr. Jason Zeng